UPM209

Multifunction three-phase meter connectable to MFC150 Rogowski coils


Highlights

  • 4 DIN modules compact version
  • Fully bi-directional four quadrants measurements for all energies and powers
  • Main electrical parameters measured and displayed for a costeffective consumption analysis
  • 4 available KITs: 30, 45, 70, 90 cm
  • 3 selectable current scales
  • Possibility to connect by PT
  • Up to 8 MB for data recording
  • Possibility to record all energy counters
  • Up to 24 parameters selectable among real time measurements for MIN/AVG/MAX recording
  • MODBUS RTU/ASCII communication by RS485 port or MODBUS TCP communication by Ethernet port
  • Possibility to manage the instrument in remote mode by WintoolNET software or by Web server interface

Applications

  • Energy audit.
  • Monitoring system and energy control.
  • Individual machine load monitoring.
  • Power peak control.
  • Switchboards, gensets, motor control centers, etc.
  • Remote metering and cost allocation.

Available Configurations

CURRENT INPUTS Rogowski inputs (3 MFC150 included) •
AUXILIARY POWER SUPPLY 85...265 VAC •
COMMUNICATION PORT
(make one choice only)
RS485 for MODBUS RTU/ASCII communication •
Ethernet for HTTP, MODBUS TCP communication •
INSTRUMENT REMOTE MANAGEMENT WintoolNET •
Web server (only for instrument with Ethernet port) •
SIGN REPRESENTATION IN MODBUS PROTOCOL
(make one choice only)
Sign bit •
2's complement •
DIGITAL OUTPUT (only for instrument with RS485 port) For alarm events or pulse emissions •
DMD VALUE CALCULATION MODE Fixed or Sliding window •
MEMORY 8 MB •
RECORDINGS Real time params MIN/AVG/MAX values (up to 24 params programmable) •
Energy counters •
WIRING MODES Three phase, 4 wires, 3 currents (3.4.3) •
Three phase, 3 wires, 2 currents (3.3.2) •
Single phase (1ph) •
THD & HARMONICS Voltage and current THD values •
Voltage and current harmonics up to 15th •
APPARENT ENERGY COUNTERS
(make one choice only)
Total counters •
Separated Inductive&Capacitive counters •

Legend
• = standard
◦ = optional

Power supply

Voltage range: 85 ... 265 VAC, Cat II
Maximum consumption: Instrument with RS485 port: 1.6 VA - 1 W
Instrument with Ethernet port: 4.5 VA - 1.6 W
Frequency: 50/60 Hz

Voltage inputs

Voltage range: 3x10/17 ... 3x285/495 VAC, Cat III 300 V
Minimum voltage value for FFT calculation: 20/35 VAC (multiplied by PT ratio in case of PT use) with direct connection

Current inputs

Maximum value: 3 selectable scales, 500/4000/20000A
Starting current (Ist) 0.3 A for FSA 500 A, 1 A for FSA 4000 A, 10 A for FSA 20000 A
Minimum current value for FFT calculation: 70 A for FSA 500 A, 400 A for FSA 4000 A, 1500 A for FSA 20000 A
2% harmonic accuracy ±2 digits

Typical accuracy

Voltage: ±0.2% reading in 10% FS...FS range (FS=Full Scale value)
Current: ±0.4% reading in 5% FS...FS range
Power: ±0.5% Reading ±0.1% FS (PF=1)
Frequency: ±0.1% reading ±1 digit in 45...65 Hz range
Active energy: Class 1 according to IEC/EN 62053-21
Reactive energy: Class 2 according to IEC/EN 62053-23

Display & keyboard

Display: Backlighted LCD, 43x29 mm
3 rows, 4 digits + symbols
Keyboard: 3 front buttons + 1 protected button

Communication ports

Type: RS485 optoisolated or Ethernet
Protocols: MODBUS RTU/ASCII in case of RS485 port
HTTP, NTP, DHCP, MODBUS TCP in case of Ethernet port
Baud rate: 300 ... 57600 bps in case of RS485 port
10/100 Mbps in case of Ethernet port

Digital output/s (DO)

Type: RS485 optoisolated or Ethernet
Protocols: MODBUS RTU/ASCII in case of RS485 port
HTTP, NTP, DHCP, MODBUS TCP in case of Ethernet port
Baud rate: 300 ... 57600 bps in case of RS485 port
10/100 Mbps in case of Ethernet port

Wire diameter for terminals

Measuring terminals (A & V): 1.5 ... 6 mm2 Terminals for digital output, AUX input, RS485 port: 0.14 ... 2.5 mm2

Size & weight

LxHxP, W: 72x90x65 mm, max 436 g

Environmental conditions

Operating temperature: -25 °C ... +55 °C (3K6)
Storage temperature: -25 °C ... +75 °C (2K3)
Max humidity (without condensation): 80%
Sinusoidal vibration amplitude: 50 Hz ±0.075 mm
Protection degree - frontal part: IP51 (granted only in case of installation in a cabinet with at least IP51 protection degree)
Protection degree - terminals: IP20
Pollution degree: 2
Installation and use: Internal

Standard compliance (for the parts applicable for UPM209)

Directives: 2006/95/EC, 2004/108/EC
Safety: EN 61010-1, EN 61010-2-030
EMC: EN 61326-1, EN 55011, EN 61000-4-2, EN61000-4-3, EN61000-4-4,
EN61000-4-5, EN61000-4-6, EN61000-4-11, EN61000-6-2