MFC150

∅8 flexible Rogowski coil

Combinable with:

  • PQM4000
  • PQM3000
  • UPM309RGW
  • UPM209RGW
  • UPT210
  • UPM307
  • UPM315
  • RPS50
  • FCA3000
  • MFC150 Rogowski Coils

    New

    • New version completely redesigned
    • Delivered already calibrated
    • Very thin coil diameter: down to 8 mm
    • Newly designed and enhanced bayonet connector including possibility to regulate calibration
    • Improved accuracy
    • Measurement uniformity at any position of the conductor inside the coil
    • Excellent degree of rejection to the external current conductor
    • Different coil colours available based on quantity

    Highlights

    • Suitable to measure currents from mA to hundreds of kA
    • High linearity
    • Wide dynamic range
    • Very useful with large size or awkward shaped conductors or in places with limited access
    • No danger from open-circuited secondary
    • Not damaged by large overloads
    • Non-intrusive, no power drawn from the main
    • Thanks to its light weight, it can be changed on the measured conductor
    • Totally shielded
    • File UL n. E231725-A1-UL

    Applications

    • Measuring devices, lab instrumentation
    • Power monitoring & control systems
    • DC ripple measurement
    • Harmonics and transients monitoring
    • Very high current monitoring

    Specifications

    Transducer
    • Coil length: from 25 to 300 cm
    • Coil diameter: 8.3 ±0.2 mm
    • Fastening: bayonet holder
    • Weight: from 150 to 500 g
    • Material: thermoplastic UL94-V0
    Electrical characteristics
    • Output level (RMS): 100 mV / 1 kA @50Hz (standard)
    • Coil resistance: from 70 to 900 Ω
    • Positioning error: better than ±1% of reading (with 15 mm diameter cable)
    • Frequency range: approx 40 Hz to 20 kHz
    • Working voltage: 1000 VRMS CAT III 600 VRMS CAT IV pollution degree 2
    • Test voltage: 7400 VRMS / 1 min
    Connection cable
    • Type: 2 x 0.15 mm + shield
    • Length: on request
    • Features: cULus approved 80 °C 1000V
    Environmental conditions
    • Operating temperature: from -30 °C to +80 °C
    • Storage temperature: from -40 °C to +80 °C
    • Protection degree: IP67
    Standards compliace
    • Safety: EN61010-1, EN61010-031, EN61010-2-031, EN61010-2-032
      EN61010-2-031, EN61010-2-032