Highlights

  • Additional voltage and current measurement channels in comparison with other standard three-phase devices./li>
  • Current inputs for CTs to grant an accurate current measurement.
  • Continuous monitoring of the power quality and Class A certified measurements for voltage characteristics.
  • Simultaneous recording of events, Min/Avg/Max LOG and energy counters.
  • Several possibilities for instrument data transmission: Ethernet, Modbus TCP, 3G network.
  • User-friendly instrument web interface with multilingual pages.

Applications

  • Power monitoring & control systems
  • Switchboards, gensets, motor control centers, etc.
  • Individual machine load monitoring
  • Power demand analysis and management
  • Harmonic monitoring
  • Remote metering and cost allocation
  • Motor inrush current studies

Specifications

Power Supply
  • Auxiliary power voltage: 85...285 VAC 50/60 Hz / 65...250 VDC
  • Auxiliary power consumption: 15 VA max
  • Fuse: 250 VAC / 500 mA T type delayed
  • Backup battery: Li-Ion, 2500 mAh (>15 min autonomy)
Measurement inputs
  • Three-phase voltage inputs for direct connection / PT: P-N: max 580 V RMS CAT III, L-L: max 1000 V RMS CAT III
  • U4 voltage input for direct connection: max 580 V RMS CAT III
  • Voltage input crest factor: 2
  • Voltage input impedance: >2 MΩ/phase
  • CT model - CT secondary: selectable 1A, 5A RMS
  • CT model - maximum current: 7A RMS
  • CT model - CT input burden: 0.04 VA
  • Clamp model - clamp output full scale: selectable 1V, 3V RMS
  • Both models - crest factor: 3
  • Frequency range: 42.5...57.5 Hz / 51...69 Hz
  • Frequency reference channel: Phase 1/Line 12 voltage
  • Sampling: Simultaneous, 51.2 kHz @50 Hz
Accuracy
  • Three-phase voltage: ±0.1% Un over 10 ... 150% Un range
  • U4 voltage: ±0.2% measurement
  • Currents: ±0.2% measurement (device)
  • Powers: ±0.2% measurement
  • Frequency: ±8 mHz
  • Harmonics: Class 1 (IEC/EN 61000-4-7)
  • Realtime clock (RTC): <1s in 24h without synchronisation; <5ms with GPS synchronisation
  • Active energy: Class 0.5S, compliant to IEC/EN 62053-22
  • Reactive energy: Class 1, compliant to IEC/EN 62053-23
I/O channels
  • Digital inputs: 11 optoisolated, 24 VDC ±20%
  • 1PPS synchronisation input: 1 optoisolated, 24 VDC ±20%
  • Analog outputs: 4 optoisolated, 4 ... 20 mADC, max load 500 Ω
  • Digital input delay time: max 10 ms
  • 1PPS input delay time: max 50 ns
  • Digital input consumption: max 7 mADC
  • 1PPS input consumption: max 1 mADC
  • Analog output reaction time: max 200 ms
Memory
  • System memory: 128 MB Flash, 256 MB RAM
  • Recording memory: 4 GB (16 GB optional)
Communication
  • Ethernet ports: 2 Auto MDIX RJ45 10/100 Base Ethernet
  • GPS port: 1 RS485 optoisolated, 9600 bps
  • GPS antenna (on PQMGPS1 module): Active patch antenna, SMA connector
  • Protocols: HTTP, HTTPS, FTP, SFTP, NTP, NMEA, Modbus TCP
  • Integrated router: GPRS/UMTS-3G/HSPA
RTC Synchronisation
  • Synchronisation system: NTP and/or GPS
Environmental conditions
  • Installation and use code: PQI-A-FI1
  • Operating temperature (limit range): FI1, 3K6 -25 ... +55 °C
  • Storage temperature: -25 ... +75 °C
  • Relative humidity: 95% max without condensing
  • Altitude: max 2000 m AMSL
Mechanical characteristics
  • Mounting: Rack 19" 3U
  • Size: Front (LxH): 482.6x133.35mm, Rear (LxHxD): 380x128x215 mm
  • Weight: 4000 g
Safety standards
  • Product compliance: IEC/EN 62586-1, IEC/EN 62586-2
  • Certification: Class A, IEC/EN 61000-4-30:2015 Ed.3 for voltage
  • Safety: CAT III power supply, insulation class 2, 600 V
  • Directive: 2006/95/EC LV, EN 61010
  • EMC: 2004/108/EC EMC, EN 50081-2, EN 50082-2, EN 61326/A1,
  • EN 55011:1998+A1:1999+A2:2002,
  • EN 61000-6-2/-4-2/-4-3/-4-4/-4-5/-4-6/-4-11

Specifications for IEC/EN 61000-4-30 compliance


Frequency (5.1)

Uncertainty ±10 mHz
Measuring range 42.5 Hz - 57.5 Hz, 51Hz - 69 Hz

Magnitude of supply voltage (5.2)

Uncertainty ±0.1% of Udin
Measuring range 10% - 150% of Udin

Flicker (5.3)

Uncertainty ±5% of reading
Measuring range 0.2 - 10 Pst

Supply voltage dips and swells (5.4)

Uncertainty Magnitude: ±0.2% of Udin
Duration: ±1 cycle

Voltage interruptions (5.5)

Uncertainty Duration: ±1 cycle

Unbalance (5.7)

Uncertainty ±0.15%
Measuring range 0.5% - 5% u20.5% - 5% u0

Harmonics (5.8)

Uncertainty IEC/EN 61000-4-7 Class I
Measuring range 10% - 200% Class 3 of IEC/EN 61000-2-4

Interharmonics (5.9)

Uncertainty IEC/EN 61000-4-7 Class I
Measuring range 10% - 200% Class 3 of IEC/EN 61000-2-4

Mains signalling (5.10)

Uncertainty ±5% of reading with measuring range 3%-15% of Udin
±0.15% of reading with measuring range 1%-3% of Udin
Measuring range 0% - 15% of Udin

Harmonics (5.5)

Uncertainty Magnitude: ±0.2% of Udin

Harmonics (5.8)

Uncertainty Consistent with "Magnitude of supply voltage (5.2)"
Measuring range 10% - 150% of Udin