The UPM310 with option "RGW" can be combined to the MFC150 Rogowski coil.
Rated voltage: 65à·250 VAC / 90à·250 VDC on request 19à·60 VDC
Consumption: 5 VA max
Maximum measurable voltage: 600 (750) VAC max L-L
Input impedance: ›1.3 MOhm
Burden: max 0.15 VA per phase
Frequency: 45 - 65 Hz
Rated current (Ib): 1 / 5 ARMS programmable
Min / max measurable current: 20 mA / 7 ARMS
Maximum overload: 10 ARMS continuous - 100 ARMS for 1 sec.
Input impedance: 0,02 Ohm approximately
Burden: max 0,5 VA per phase
Insulation voltage: 150 VAC max between phases
Rogowski input: 200à·49995 A on request
Voltage: ±0.1% reading ±0.03% full scale
Current: ±0.1% reading ±0.05% full scale
Active power: ±0.5% reading ±0.1% full scale (PF=1)
Power factor: 1% reading (0.5 inductive - 0.8 capacitive)
Active energy: 1% reading (0.5 inductive - 0.8 capacitive)
Frequency: ±0.05% reading ±2 digits from 45 to 65 Hz
Display: high brightness 13,8 mm LED display, three lines, 4 alphanumeric digits
Keypad: 4 push-buttons
Type: on-board non-volatile FLASH, 128 kB or 2 MB
Type: 1 selectable RS232 or RS485, optoisolated 1 available for plug-in comm. boards
Baud rate: programmable from 300 to 57600 bps
Type: with battery backup
Accuracy: ± 30 ppm
Type: 2 isolated optomos (50V - 300mACA-CC)
Operating temperature: from -15 °C to +60 °C
Storage temperature: from -30 °C to +75 °C
Relative humidity: 80% max. without condensation
Material: metal enclosure
Protection degree: IP54 (front panel); IP20 (terminals)
Terminals: standard pluggable terminals (EU) on request barrier terminal strips (USA)
Size / weight: DIN version: 96 x 96 x 130 (mm) / 750 gr
transducer version: 90 x 90 x 130 (mm) / 800 gr
Safety: 73/23/EEC, 93/68/EEC directives, EN61010-1
EMC: 89/366/EEC directive and following modifications 93/31/EEC and 93/68/EEC, EN50081-2, EN50082-2, EN61326/A1