Algodue Elettronic Network Analysers and Energy Meters
UEM80 "¹UEM80-4D R, UEM80-D M, UEM80-4D E›
80A three phase energy counter with built-in communication
Highlights
- UEM80-2D R for RS485 Modbus RTU/ASCII communication
- UEM80-D M for M-Bus communication
- UEM80-2D E for Ethernet (Modbus TCP) communication
- Direct connection up to 80 A
- Fully bi-directional 4-quadrant measurements for all energies and powers
- For 3 / 4 wire networks with balanced or unbalanced load (UEM80-4D R and UEM80-4D E only for 4 wire networks)
- S0 output for energy pulse emission
- Class B according to EN 50470-3
- Available with MID certification
Applications
- Totalization of the electric energy in the industry for each single line or machine.
- Measurement of energy generated by renewable sources such as solar, eolic, etc.
- Accounting and billing of consumptions in camp sites, malls, residential areas, naval ports, etc.
- Totalization of the electric consumption in hotels, congress centers, exhibition fairs.
- Accounting of the consumptions in buildings with executive office services.
- Internal allocation of the consumptions in timeshare civilian and industrial buildings.
- Realization of energy monitoring systems.
- Remote survey of the consumptions and compute of the costs.
Technical features
Power Supply
- Power supplied from the voltage circuit
- Nominal measurement voltage ±20%
- Max consumption (for each phase):
UEM80-4D R, UEM80-4D E: 3,5 VA - 1 W
UEM80-D M: 7,5 VA - 0,5 W
- Nominal frequency: 50/60 Hz
Voltage range & frequency
- 3x230/400...3x240/415 V 50/60 Hz
Current
- Starting current Ist: 20 mA
- Minimum current Imin: 250 mA
- Transitional current Itr: 500 mA
- Reference current Iref (Ib): 5 A
- Maximum current Imax: 80 A
RS485 Modbus communication
- Port: RS485
- Protocol: Modbus RTU/ASCII
- Communication speed: 300 ... 57600 bps
M-Bus communication
- Port: wired (EN 1434-3)
- Protocol: M-Bus
- Communication speed: 300 ... 38400 bps
- Unit load: 1
Ethernet communication
- Port: 10/100 Base T
- Protocol: HTTP, NTP, DHCP, Modbus TCP
- Communication speed: 10/100 Mbps
- Data recording
- Web server
Accuracy
- Active energy class B according to EN 50470-3
- Reactive energy class 2 according to IEC/EN 62053-23
S0 output (no ETHERNET model)
- Passive optoisolated
- Maximum values: 27 VDC- 27 mA
- Pulse length: 50
Tariff input (no ETHERNET model)
- Active optoisolated
- Voltage range for tariff 2: 80 ... 276 VAC-DC
Metrological LED
- Meter constant: 1000 imp/kWh
- Pulse length: 10 ± 0.2 ms
Environmental conditions
- Operating temperature: -25 °C ... +55 °C
- Storage temperature: -25 °C ... +75 °C
- Humidity: 80% max without condensation
- Protection degree: IP51 frontal part -IP20 terminals
©1993-2021 - Measurement & Control Solutions CC - All rights reserved