UEC1P5-X

6A three phase 3/4 wire energy counter


Highlights

  • For 1 or 5A CT
  • Programmable CT ratio
  • Fully bi-directional four quadrants measurements for all energies and powers
  • For 3 / 4 wire networks with balanced or unbalanced load
  • Class B according to EN 50470-3
  • Tariff input
  • 2 S0 outputs for energy pulse emission
  • LCD display with 8 main digits
  • Optical port for communication
  • Available with MID certification

Applications

  • Totalization of the electric energy in the industry for each single line or machine.
  • Measurement of energy generated by renewable sources such as solar, eolic, etc.
  • Accounting and billing of consumptions in camp sites, malls, residential areas, naval ports, etc.
  • Totalization of the electric consumption in hotels, congress centers, exhibition fairs.
  • Accounting of the consumptions in buildings with executive office services.
  • Internal allocation of the consumptions in timeshare civilian and industrial buildings.
  • Realization of energy monitoring systems.
  • Remote survey of the consumptions and compute of the costs.

Technical features

Power Supply
  • Power supplied from the voltage circuit
  • Nominal measurement voltage ±20%
  • Max consumption (for each phase): 7,5 VA - 0,5 W
  • CT burden (for each phase): 0,04 VA

  • Nominal frequency: 50/60 Hz

Voltage & Frequency
  • Nominal values:
    A) 3x230/400 V 50 Hz
    B) 3x240/415 V 50 Hz
    C) 3x230/400 V 50/60 Hz
    D) 3x230/400...3x240/415 V 50/60 Hz
Current
  • Starting current Ist: 2 mA
  • Minimum current Imin: 10 mA
  • Transitional current Itr: 50 mA
  • Reference current Iref (In): 1 A
  • Maximum current Imax: 6 A
Accuracy
  • Active energy class B according to EN 50470-3
  • Reactive energy class 2 according to IEC/EN 62053-23
S0 output (no ETHERNET model)
  • 2 passive optoisolated
  • Maximum values: 250 VAC-DC - 100 mA
  • Pulse length: 50 ±2ms
Tariff input (no ETHERNET model)
  • Active optoisolated
  • Voltage range for tariff 2: 80 ... 276 VAC-DC
Metrological LED
  • Meter constant: 1000 imp/kWh
  • Pulse length: 10 ±2 ms
Environmental conditions
  • Operating temperature: -25 °C ... +55 °C
  • Storage temperature: -25 °C ... +75 °C
  • Humidity: 80% max without condensation
  • Protection degree: IP51 frontal part -IP20 terminals