Algodue Elettronic Network Analysers and Energy Meters
UEC1P5-X
6A three phase 3/4 wire energy counter
Highlights
- For 1 or 5A CT
- Programmable CT ratio
- Fully bi-directional four quadrants measurements for all energies and powers
- For 3 / 4 wire networks with balanced or unbalanced load
- Class B according to EN 50470-3
- Tariff input
- 2 S0 outputs for energy pulse emission
- LCD display with 8 main digits
- Optical port for communication
- Available with MID certification
Applications
- Totalization of the electric energy in the industry for each single line or machine.
- Measurement of energy generated by renewable sources such as solar, eolic, etc.
- Accounting and billing of consumptions in camp sites, malls, residential areas, naval ports, etc.
- Totalization of the electric consumption in hotels, congress centers, exhibition fairs.
- Accounting of the consumptions in buildings with executive office services.
- Internal allocation of the consumptions in timeshare civilian and industrial buildings.
- Realization of energy monitoring systems.
- Remote survey of the consumptions and compute of the costs.
Technical features
Power Supply
- Power supplied from the voltage circuit
- Nominal measurement voltage ±20%
- Max consumption (for each phase): 7,5 VA - 0,5 W
- CT burden (for each phase): 0,04 VA
- Nominal frequency: 50/60 Hz
Voltage & Frequency
- Nominal values:
A) 3x230/400 V 50 Hz
B) 3x240/415 V 50 Hz
C) 3x230/400 V 50/60 Hz
D) 3x230/400...3x240/415 V 50/60 Hz
Current
- Starting current Ist: 2 mA
- Minimum current Imin: 10 mA
- Transitional current Itr: 50 mA
- Reference current Iref (In): 1 A
- Maximum current Imax: 6 A
Accuracy
- Active energy class B according to EN 50470-3
- Reactive energy class 2 according to IEC/EN 62053-23
S0 output (no ETHERNET model)
- 2 passive optoisolated
- Maximum values: 250 VAC-DC - 100 mA
- Pulse length: 50 ±2ms
Tariff input (no ETHERNET model)
- Active optoisolated
- Voltage range for tariff 2: 80 ... 276 VAC-DC
Metrological LED
- Meter constant: 1000 imp/kWh
- Pulse length: 10 ±2 ms
Environmental conditions
- Operating temperature: -25 °C ... +55 °C
- Storage temperature: -25 °C ... +75 °C
- Humidity: 80% max without condensation
- Protection degree: IP51 frontal part -IP20 terminals
©1993-2021 - Measurement & Control Solutions CC - All rights reserved