Algodue Elettronic Network Analysers and Energy Meters
UEM40, UEM40-2C R, UEM40-2C M
40A single phase 2 wire energy meter
Highlights
- Direct connection up to 40 A
- Fully bi-directional 4-quadrant measurements for all energies and powers
- UEC40-2C for a simple energy meter without built-in communication
- UEM40-2C R for RS485 Modbus RTU communication
- UEM40-2C M for M-Bus communication
- High reliability
- 1 DIN module compact size
- Quick installation
- S0 output for energy pulse emission
- LCD display with 7 main digits
- Available with MID certification
Applications
- Totalization of the electric energy in the industry for each single line or machine.
- Measurement of energy generated by renewable sources such as solar, eolic, etc.
- Accounting and billing of consumptions in camp sites, malls, residential areas, naval ports, etc.
- Totalization of the electric consumption in hotels, congress centers, exhibition fairs.
- Accounting of the consumptions in buildings with executive office services.
- Internal allocation of the consumptions in timeshare civilian and industrial buildings.
- Realization of energy monitoring systems.
- Remote survey of the consumptions and compute of the costs.
Technical features
Power Supply
- Power supplied from the voltage circuit
- Nominal measurement voltage ±20%
- Max consumption: 1.5 VA - 1 W
- Nominal frequency: 50/60 Hz
Voltage range & frequency
- Nominal values: 230 V 50/60 Hz
Current
- Starting current Ist: 20 mA
- Minimum current Imin: 250 mA
- Transitional current Itr: 500 mA
- Reference current Iref (Ib): 5 A
- Maximum current Imax: 40 A
RS485 Modbus communication
- Port: RS485
- Protocol: Modbus RTU
- Communication speed: 2400, 4800, 9600, 19200, 38400 bps
- Unit load: 1/8
M-Bus communication
- Port: wired (EN 1434-3)
- Protocol: M-Bus
- Communication speed: 300, 2400, 9600 bps
- Unit load: 1
Accuracy
- Active energy class 1 according to IEC/EN 62053-21 (NO MID)
- Active energy class B according to EN 50470-3 (MID)
- Reactive energy class 2 according to IEC/EN 62053-23
S0 output
- Passive optoisolated
- Maximum values: 27 VDC - 27 mA
- Meter constant: 500 imp/kWh
- Meter constant: 1000 imp/kWh
The measuring unit (imp/kWh, imp/kvarh, imp/kVAh) changes according to the assigned counter (kWh, kvarh, kVAh)
- Pulse length: 100 ±0.5ms
Metrological LED
- Meter constant: 5000 imp/kWh
- Pulse length: 4 ± 0.1 ms
Environmental conditions
- Operating temperature: -25 °C ... +55 °C
- Storage temperature: -40 °C ... +75 °C
- Humidity: 80% max without condensation
- Protection degree: IP51 frontal part -IP20 terminals