Our DC600 Current Probe measures up to 600 amps DC (as well as 400 amps AC). Self-powered via our meter, so there are NO batteries that can run down during a measurement session.
The DC600 Current Probe can measure up to 600 amps DC (as well as 400 amps AC). Self-powered via our PowerSight analyzer, so there are NO batteries that can run down. Large capacity jaws for large cables.
Can measure from 5 to 600 Amps DC current for most industrial DC measurement jobs
No batteries required, because power is supplied by PowerSight. This means that the probe will not stop during a long monitoring session.
Large jaws to be able to clamp around large cables and bus bars.
Can also measure to 400 Amps AC
[Note: These probes use the Hall Effect and therefore must be zeroed by the user prior to every use]
[Note: The DC600 does an adequate job of measuring AC current, but is less accurate than our AC current probes.]
Category
Notes
Measurement Ranges:
5 to 600 amps DC 5 to 400 amps AC
Accuracy (after zeroing):
±1 amp ±2% from 5 to 400 amps DC or AC ±1 amp ±3% from 400 to 600 amps DC
Power Required:
Power to the DC600 is supplied by PowerSight
Inside Clamping Capacity:
one cable up to 1.18" diameter two cables up to 0.95" diameter