PK2513 complete Power Quality Analysis Systemincludes PS2500 Power Analyzer, three HA1000 high-accuracy current probes, and the SCAS4 soft-shell carrying case.
The PK2513 is a good package for basic power studies, energy audits, load studies, and more. Wide-range highly-accurate clamp-on current probes allow you to get the most accurate answers for AC power measurements.
Advanced PowerSight Manager software improves your efficiency and eliminates sources of error at each stage of the monitoring process. CAT IV safety rating and wireless remote control via Bluetooth for even greater safety. SD memory card for redundant storage and essentially unlimited logging capacity.
For improved speed and the productivity of a full keypad and back-lit display, choose thePS3500 Power Quality Analyzer
PK2513 complete Power Logging Systemincludes PS2500 Power Analyzer, three HA1000 high-accuracy current probes, and the SCAS4 soft-shell carrying case. The PK2513 is a good analysis system for basic power studies, energy audits, load studies, and more.
The soft-shell carrying case has multiple compartments. This provides separate storage for the analyzer, manuals, voltage leads, and current probes (as shown in the photos above).
PK2513 Analysis System includes:
PS2500 PowerSight Power Logger / Data Logger
Three HA1000 amp current probes
SCAS4 Soft shell carry case
DXV deluxe voltage leads with Jumbo Alligator clips
AC Charger (specify 120 or
240 volt version)
PSM PowerSight Manager Software for PC
Measure and log all basic power measurement types: V, A, W, VA, VAR, kWH, PF, Hz, etc. [Note: add Harmonics Option to log THD].
Wide range of operating modes:
Able to evaluate all common power systems: 3 phase Wye, 3 phase Delta (including 4-wire, open, and grounded), split-phase, single phase, quad single phase (using same source) , 3PT/3CT, 3PT/2CT, 2 current power, DC.
The included Advanced PowerSight Manager software (PSM-A) improves your efficiency and eliminates sources of error at each stage of the monitoring process:
Benefit from the safety rating of 1000V CAT IIII, 600V CAT IV and Bluetooth Wireless Communications (remote viewing/control of the display without the burden of wearing PPE).
SD Memory for redundant storage and essentially unlimited logging capacity.
Extend the measurement range with the use of our industry-widest array of accessories and options:
First rate technical support, direct from the manufacturer to you!
Category | Notes |
---|---|
Size: | PS4500 Analyzer: 3.88" (9.86 cm) W x 7.72" (19.61 cm) L x 1.58" (4.01 cm) Deep at bottom end 2.14" (5.44 cm) Deep at top end |
Weight | PS4500 Analyzer: 1.1 lbs (0.5 kg) |
Operating Range | 32 - 122 degrees F (0 - 50 degrees C) Relative humidity to 70% (non-condensing) |
Power Requirement | 12V DC @ 500 mA. |
Battery Life | 8-10 hours after 4 hour charge |
Battery Type | Li-ion |
Sampling Rate | 16 microseconds for Voltage and Current |
Safety | 600V CAT IV, 1000V CAT III |
SD Card Slot | Accepts SD Cards to 32GB (SDHC) |
Logging Period (Resolution) | 1 Second - 99 Minutes (set by user) |
Logging Duration (Length of session) | Up to 2 years, depending on memory allocation |
Internal Data Retention | 8 years |
Other Features | Crest Factor, K Factor, Peak Demand Period, Peak Demand of Peak, Demand Period. |
Category | Notes |
---|---|
Measurement Range | 1 to 1000 volts (using included voltage probes), to 15,000 volts (with optional 15KVP voltage probes), to 6 megavolts (with input ratios) |
Display Resolution | 1V (below 400V), 10V (400V to 3.99KV), 100V (4.0KV to 39.9KV) |
Accuracy | 0.5% of reading ±0.3 Vrms |
Category | Notes |
---|---|
Measurement Range | 2 milliamp (with optional HA-GFD), to 1,000 amps (using included HA1000 current probes), to 6 megamps (with input ratios) |
Display Resolution | 1 amps (below 1000A), 10 amp (1000 amps and above) |
Meter Display Range | 1A (PS2500); 0.1A (PS3500) |
Accuracy | ±0.5 % of reading including accuracy of HA1000 probes |